The Aprilaire 700M is a fan-powered whole-house humidifier with a manual dial control. Set the dial by the outdoor temperature printed on it (35% at 20°F, 25% at 0°F, 15% at −20°F), replace the Water Panel (part 35) once a year, and turn the dial to OFF when the air conditioning takes over. There is no bypass damper to switch. Air Comfort Service has serviced St. Louis homes since 1969 and services the 700M along with other humidifiers.
How the Aprilaire 700M works
The 700M is an evaporative humidifier with a fan of its own. Water enters at the top, spreads across a distribution tray, and runs down over a Water Panel. The built-in fan draws warm, dry air from your furnace through the wet panel and sends it back into the duct carrying moisture as vapor. Nothing gets heated, nothing gets misted, and there is no tank to fill.
Because the fan does the work, the 700M needs no bypass duct and no seasonal damper. It mounts on the furnace plenum, plugs into a standard 120-volt outlet, and is rated at 18 gallons of water a day for homes up to 4,200 square feet (the bypass 600M is rated at 17 gallons and 4,000 square feet). The motor is permanently lubricated; the manual says it never needs oil.
Water that doesn't evaporate runs to the drain and carries dissolved minerals with it. That trickle is the design working. The saddle valve on the water line should be fully open; a small orifice at the feed tube sets the flow rate.
What to set the dial to
The 700M's Manual Humidifier Control is a dial marked OFF, 15, 25, 35, and 45 percent, with Aprilaire's guide printed across the top:
Colder glass condenses more moisture, so the setting drops as the temperature does. Fog or frost on the inside of your windows means one step down. Static shocks and dry air mean one step up. Before a cold snap, lower it a few hours ahead.
For most St. Louis winter days, 35% is the setting, with 25% for the coldest nights.
How to tell if it's running.
The 700M has no indicator lights. Three checks tell you what you need to know.
- Is the furnace fan running? The 700M's own fan only runs when the furnace blower runs and the control calls for humidity. No heat call, no humidity.
- The two-click check. With the furnace fan running, turn the dial slowly clockwise until the humidifier clicks on, then counterclockwise until it clicks off. Your indoor humidity is between those two settings.
- Look at the drain. While it runs, you should see a small, steady stream at the drain line. No stream means water isn't getting through: a closed saddle valve, a clogged strainer or orifice, or a solenoid that isn't opening.
You can also hear the 700M. The fan has a sound of its own, separate from the furnace blower, when the unit is running.
The Water Panel
The Water Panel traps minerals as water evaporates, and after a heating season it's crusted and moves less air and less water. Aprilaire calls for a new Water Panel at least once a year on the 700M. The replacement is part number 35, the same panel the 600M uses.
A worn panel is one of the most common reason a homeowner tells us "the humidifier stopped working." Other common causes include poor water flow.
The full annual service, from the manual's required maintenance list for the 700 series:
- Dial to OFF, power cord unplugged, water supply shut off
- Cover assembly unlatched from the base, evaporative assembly pulled out by the top
- Distribution tray unsnapped and cleaned of mineral deposits
- Old Water Panel out, scale control insert cleaned, new Water Panel 35 in
- Feed tube flexed and inspected; recommended to replace if stiff or brittle
- Drain line checked.
- Inline strainer and orifice inspected and cleared
- Cover latched, power and water back on, dial back to your setting, operation confirmed with the furnace fan running
The 700M carries a 120-volt electric shock warning in the manual for anyone opening it. That is why Air Comfort Service does this as a service visit.
Summer shutdown
Turn the dial to OFF. That's the whole shutdown on a 700M; with no bypass duct there is no damper to close.
Use the guide on the dial: 35% at 20°F outside, 25% at 0°F, 15% at −20°F. Turn it down one step if your windows fog on the inside.